3-Phase Meter Telstar

The smart-me Telstar 80A is a MID energy meter with an integrated WiFi or mobile communications interface for transmitting real-time data. The meter connects smart-me cloud and automatically synchronises the data in an encrypted format. This is the easiest way of visualising energy consumption in real time, billing the energy use and intelligently controlling your own consumption. Using the smart-me cloud, the collected measurement data can be exported to and processed in a variety of third-party systems.

Functions

  • Encrypted real-time data connection to the intelligent smart-me cloud

  • Remote switches, time switches and condition-based switches via the outputs

  • Comprehensive energy data management and visualisation, automatic billing as well as intelligent control and alarms using the smart-me cloud

  • Floating contact outputs for controlling external devices (one of them with an integrated 8A relay)

  • Floating contact input for tariff signal or digital input

  • Easy installation with the free smart-me app for Android and iOS

  • Compatible with and automatically connected to the smart-me head-end system (HES) for the smart meter rollout

  • Interface to a variety of third-party systems such as billing and building management systems as well as smart home systems (via API, CSV, MSCONS, IS-E, etc.)

  • Directly installed SIM card with data volume for ten years included in the purchase price (mobile communications version only)

Technical Data

Reference current 5 (80) A

Product certification CE, MID 2014/32/EU, CH load profile/reactive energy, RED

Measuring range 5 –18, 400 W per phase

Accuracy class Class B (1%)

Meter type Four-quadrant meter (purchase and delivery) for active and reactive energy

Measured values Active energy (kWh), active power (kW), reactive energy (kVArh), reactive power (kVAr), current (A), voltage (V), power factor (cosφ), switch status

Tariffs Two via digital tariff input or use of any virtual tariffs in the cloud

Digital input Floating tariff input (12 VDC/230 VAC)

Digital outputs Floating outputs (SG ready), 12 VDC/230 VAC, S0-0<0.4 W S-1<1,500 W

WiFi standard 802.11 b/g/n

WiFi security standard WEP, WPA-PSK/WPA2-PSK

Mobile communications (optional) LTE Cat.M1/NB-IoT

S0 pulse weight 1,000 pulses per kWh (configurable to 10,000 pulses/kWh)

Data storage Two months

Temperature range -25 to +70°C

Measuring device category CAT III

IP class IP 20, IP 51 (front)

Dimensions Five modules, 90 x 90 mm

Rel. humidity Average 75%, without condensation / short term 95%, without condensation

Assembly DIN rail

Server location Switzerland

Potential-Free Output

The output can be used as an impulse exit (standard type) or as a switchable potential-free contact.

Further information: Output

Digital Input

The digital input can be used as a tariff input (standard) or as a digital input.

Further information: Input

Display

The meter has a rolling display. The items described below are displayed in sequence. After the last point, it starts again at point 1:

  1. Meter reading (OBIS code followed by meter reading)

1.8.1 (A+) Active energy import tariff 1

1.8.2 (A+) Active energy import tariff 2

2.8.1 (A+) Active energy delivery tariff 1

2.8.2 (A+) Active energy delivery tariff 2

5.8.0 (Q1) Total inductive reactive energy consumption

6.8.0 (Q2) Total capacitive reactive energy consumption

7.8.0 (Q3) Total inductive reactive energy delivery

8.8.0 (Q4) Total capacitive reactive energy delivery

  1. Firmware (OBIS code followed by information)

C.1.6 Ch: 9718 Firmware checksum

0.2.0 V 1.1 Firmware version

  1. Error display (OBIS code followed by error messages)

C.60.9 Fraud Flag (possible attempted fraud detected)

PhL: 1 only phase L1 connected

PhL: 2 only phase L2 connected

PhL: 3 only phase L3 connected

PhL: 23 Phase L1 not connected

PhL: 13 Phase L2 not connected

PhL: 12 Phase L3 not connected

Correct phase sequence: Numbers light up statically

Incorrect phase sequence: numbers flash

Measurements

Wiring

T1 button for installation

T2 special functions

In short: If T2 is pressed> 2s, the green LED lamp switches on / off. If this is activated, it shows the connection status

Glowing green: connected to smart-me cloud

Flashing green: connection is currently established, at the moment no connection

Long: If T2 is pressed> 8s, the display of the power is switched between active and reactive power. In addition, the calibration pulse LED alternates between active energy and reactive energy.

Very long: If T2 is pressed> 14s, the S0-0 pulse output is switched between active power and reactive power.

ATTENTION: This setting only changes the display, not in the smart-me cloud (app and website). If the reactive energy is to be displayed in the cloud, this must be done in the general settings.

E1 tariff input, potential-free

Tariff 1: 0V (or not connected)

Tariff 2: 12VDC / 230VAC

adjustable as a digital input

S0-0 S0 pulse output, potential-free

Power MOSFET with PMAX = 0.4 W

adjustable as a digital output

S-1 power output, potential-free

Relay with PMAX = 1,500 W

Measured values (Obis codes)

The following measured values are recorded by the meter and can be accessed in the cloud and via the API.

Messwerte (inkl. Obiscodes) 3-Phasen Zähler V1

Downloads

2020-08-21 smart-me 3-PHasen Meter 80A Telstar Datenblatt DE ES-Low.pdf

Deutsch

2020-08-21 smart-me 3-PHasen Meter 80A Telstar Datenblatt EN ES-Low.pdf

Englisch

2020-10-22 smart-me 3-PHasen Meter 80A Telstar Datenblatt FR ES-Low.pdf

Français

2020-10-22 smart-me 3-PHasen Meter 80A Telstar Datenblatt IT ES-Low.pdf

Italiano