Configure multilevel load management

Configuring the multilevel load management (MLM)

Multilevel load management is configured in the "Multilevel load management" area in the main navigation bar

The function enables:

Definition of terms

Multilevel load management can be regarded as a tree, whereby the following terms and usages exist:


The trunk and branches can fulfil several functions:


Unmeasured load:

An unmeasured load corresponds to a producer or consumer that does not correspond to a Pico charging station group. In order to be able to dynamically take this production or load into account, a meter hardware must be provided as a reference. (Measured branch)

The branch can also be statically limited without a reference meter, but must be limited to a functional maximum, taking into account the base load, for protection.

Typical branches with unmeasured loads: 

Add or delete branch

Add:

Select the trunk or branch and create an additional branch using "Add branch".

Delete:

By selecting the corresponding branch and the "Delete" function, the selected branch and all branches attached to it are deleted.

To ensure that the following is retained, the branches and groups can be attached to another branch or trunk beforehand using the drag & drop function.




Add charging station groups to the tree

The charging station groups for the MLM that have not yet been assigned and correctly configured can be found on the right-hand side.

These can be added to the branches using the drag & drop function and can also be moved within the configuration using drag & drop.


Note: 

A prerequisite for use in the MLM is that the connection failure setting is configured to "Max. current (per group)".

This can be adjusted on a Pico charging station in the "Configuration".


Solar optimisation and minimum current per charging group

Branch configuration:

Solar optimisation is possible once on the trunk (area-optimised) or several times in parallel on branches with active unmeasured loads, e.g. house connections.

Depending on the selection, the solar surplus is optimised on all charging station groups or only on some of the charging station groups.




Group configuration:

In order for solar optimisation to have the appropriate effect, the station groups to be optimised must be temporarily assigned a reduced minimum charging current; this minimum charging current is defined on the corresponding charging group (group configuration) and corresponds to the maximum possible grid consumption for the charging group in the defined hours.

At the same time, the setting of the minimum charging current can also be used for peak load interruption.

Each group can be configured in different ways.

Groups with a higher minimum charging current are prioritised in the distribution of available grid power.

Saving and activating the configuration

The changes in the configuration are only saved if the configuration is also activated.

If activation cannot be carried out due to incorrect configuration, this may be due to the following points:

Deleting the MLM configuration

The configuration of an MLM can be deleted in its entirety at the touch of a button to create a new configuration.

Configuration of the load shedding

The MLM has an integrated load shedding controller.

This control can be used instead of the hardware inputs on the rear of the Pico charging stations. 

Notes: 

The function enables one or more digital signals from energy suppliers to be interpreted and a reduced charging power to be allocated to all charging station groups of the MLM.

The control signals are wired to one or two nearby meter inputs (E1).

The smart-me Telstar CT and Telstar 80A hardware are compatible for this.

Note: 

In order for the inputs to be used, they must be configured to "digital input" on the hardware side.
(Meter settings, E1 --> Digital input)

Control configurations:

With only one signal:

With two signals:


Percentages apply to EnWG14a in Germany:

For 22kW systems, a reduction of 82% corresponds to the promise of 4200W minimum power per appliance in the installation.

For 11kW systems, a reduction of 73% corresponds to the promise of 4200W minimum power per device in the installation.

Signal interpretation:

The signal can be interpreted in different ways.

If the signal is removed by the energy supplier in the load shedding case (230V --> 0V), "Low active" is the correct configuration.

If the signal from the energy supplier is applied in the load shedding case (0V --> 230V), "High active" must be selected.

Activate and deactivate the MLM processor

The configuration of an MLM can be deactivated and re-activated.

Choose if the MLM shall be active or inactive and then store the configuration to submit the decision to the processor.

Example configuration: House with e-mobility outlet + garage lighting, solar system and midday peak shaving

The subordinate emobility output is actively measured here to take the garage lighting into account. The charging groups should thus react dynamically to the garage lighting.

In order for the solar optimization to be effective, the minimum amount of charging current is reduced throughout the day.

Example configuration: Area with several houses, solar systems and e-mobility outlets

HAK TG1: House connection for building 1 in the area

TG1 e-mobility feed

Visitor parking spaces in the area (public charging stations)

Tenant parking spaces in the area

Untreated installation parts: