In some projects, after installation, the current transformer terminals are sometimes forgotten to be closed.
Solution: In the Smart-me portal, select "Meter," then click on the gear icon, go to "General Settings," enter the correct ratio, and save it.
Smart-me recommends entering the transformer ratio in the cloud as it is noted on the transformer itself, for example, 300:5.
Important: Historical data will not be adjusted.
For PV meters, the current usually has a negative sign.
Generally, pure consumption meters have positive signs for currents.
The balance meter may have different signs depending on the situation.
For purchased power, these are usually positive.
For delivered power, these are usually negative.
If the cos Phi <0.5, it is likely that the voltage taps do not match the phases or the direction of rotation has been reversed.
Our devices have a 1% measurement accuracy according to the MID standard.