3-Phase Meter Telstar CT
The smart-me Telstar CT is an MID-certified energy meter with integrated WiFi interface for the transmission of real-time data and with connection for external converters. The meter synchronises the measured values automatically and encrypted in the smart-me cloud. The smart-me portal can be used to further process the data. Alternatively, they can be exported and processed in third-party systems via our open interface. The meter has two digital outputs for controlling devices with a dry contact.
Functions
Commissioning with the free smart-me app.
Inputs for external current transformers from 0.01 to 6A output
Create bills with the smart-me billing tool.
Control with if/then actions or event actions
Dry contact outputs for control of external devices, one of them with 8A relay
Floating contact input for tariff signal or digital input
Interfaces via API, CSV, MSCONS and IS-E
Encrypted real-time data connection to the smart-me cloud
Technical Data
Technical requirements for the current transformers
A wide variety of current transformers can be used with the Telstar CT. The basic requirements are as follows:
Current transformer ratio: 1: 1 to 20,000: 1 to 5: 5 to 20,000: 5
The secondary number may be an integer number between 1 and 5
The primary number may be an integer number between 1 and 20'000Output current: 1A to 5A
Output power: at least 1VA or higher
Type: open or closed
Accuracy class: 1 or better*
* For billing purposes, calibrated converters are required that must meet at least class 0.5 or better. This is achieved almost exclusively with closed type current transformers.
Suggestionsfor transformers and accessories can be found on the page: Current transformers and accessories
Display
Value / Symbol Description
1.8.1 OBIS code for the displayed meter reading
T1 Active tariff (tariff 1 or tariff 2)
Arrow Direction of flow (right-hand reference / left-hand delivery)
Signal (Bars) WiFi Signal strength
0000053.2 Meter reading
5520W Current measured power with unit
kWh Unit of the displayed meter reading
The meter has a rolling display. The items described below are displayed in sequence. fter the last point, the first point is displayed again.
Meter reading (OBIS code followed by meter reading)
1.8.1 (A+) Active energy import tariff 1
1.8.2 (A+) Active energy import tariff 2
2.8.1 (A+) Active energy delivery tariff 1
2.8.2 (A+) Active energy delivery tariff 2
1.8.0:5A (A +) active energy total import 5A basis
2.8.0:5A (A-) active energy total delivery 5A basis
5.8.0 (Q1) Total inductive reactive energy consumption
6.8.0 (Q2) Total capacitive reactive energy consumption
7.8.0 (Q3) Total inductive reactive energy delivery
8.8.0 (Q4) Total capacitive reactive energy delivery
Converter factor (OBIS code followed by information)
0.4.2 Converter factor (including S0 pulses / kWh)
Firmware (OBIS code followed by information)
C.1.6 Ch: 2218 Firmware checksum
0.2.0 V 1.1 Firmware version
Error display (OBIS code followed by error messages)
C.60.9 Fraud Flag (possible attempted fraud detected)
PhL: 1 only phase L1 connected
PhL: 2 only phase L2 connected
PhL: 3 only phase L3 connected
PhL: 23 Phase L1 not connected
PhL: 13 Phase L2 not connected
PhL: 12 Phase L3 not connected
Correct phase sequence: Numbers light up statically
Incorrect phase sequence: Numbers flash
Measurements and Wiring
*.DXF and *.DWG files of the meter, can be found in the ZIP archive under downloads
Dimensions [mm]
Wiring diagram
*Stromwalder = Current Transducers
Key functions
T1 button for installation
When T1 button is pressed for 10 seconds, it creates a local WiFi for installation
T1 + T2 Restart
Press T1 and T2 buttons simultaneously for 10 seconds to force a reboot.
T2 special functions
In short: If T2 is pressed for >2s, the green LED lamp switches (from on to off or from off to on). If this is activated, it shows the connection status
Glowing green: connected to smart-me cloud
Flashing green: connection is currently established, at the moment no connection
Long: If T2 is pressed> 8s, the display of the power is switched between active and reactive power. In addition, the calibration pulse LED alternates between active energy and reactive energy.
Very long: If T2 is pressed> 14s, the S0-0 pulse output is switched between active power and reactive power.
Note: This setting only changes the display, not in the smart-me cloud (app and website). If the reactive energy is to be displayed in the cloud, this must be done in the general settings.
Configuring inputs and outputs
The smart-me meter has two outputs and one input, which can be used as pulse inputs and outputs or as a switchable potential-free contact. Details can be found here.
Configuring inputs and outputs
The Telstar CT has two digital outputs and one digital input, which can be used as pulse inputs and outputs or as a switchable dry contact. Details can be found on the Inputs and Outputs wiki page.
The Telstar CT has a relay at one digital output, which can switch up to 8A.
Mesh-Technologie
In the event of very weak or no WiFi reception, the Telstar 80A automatically connects to another neighboring meter within range via the mesh function. This meter then takes over communication with the smart-me cloud. The mesh technology ensures that the meters have a higher availability to the smart-me Cloud. It is not possible to deactivate the mesh function on the meters. Specific restrictions apply when Modbus TCP is enabled.
Current Transducers and Accessories
Suggestionsfor transformers and accessories can be found on the page: Current transformers and accessories
Shipping information
Item number: 212062
Article name: 3-Phasen Energiezähler Telstar CT MID Wifi
Customs tariff number: 9028.3019
Weight with packaging: 315g
Downloads and certificate of conformity
Wiring Diagram ZIP Files (*.DXF and *.DWG files of the meter, can be found in the ZIP archive)